3UF7000-1AB00-0
BASIC UNIT SIMOCODE PRO C;

From SIEMENS

Basic unit SIMOCODE pro C, PROFIBUS DP interface 12 Mbit/s, RS 485, 4I/3O freely parameterizable, Us: 24 V DC, input for thermistor connection Monostable relay outputs
Product brand nameSIRIUS
Product designationMotor management system
Design of the productbasic unit 1
Product type designationSIMOCODE pro C
General technical data
Product function
Bus communicationYes
data acquisition functionYes
Diagnostics functionYes
Password protectionYes
Test functionYes
maintenance functionYes
Product component
input for thermistor connectionYes
Digital inputYes
input for analog temperature sensorsNo
input for ground fault detectionNo
Relay outputYes
Product extension
Temperature monitoring moduleNo
Current measuring moduleYes
Current/voltage measuring moduleNo
failsafe digital I/O moduleNo
Ground fault monitoring moduleNo
Control unit with displayNo
Control unitYes
analog I/O moduleNo
Consumed active power5 W
Insulation voltage
with degree of pollution 3 rated value300 V
Surge voltage resistance rated value4 000 V
Protection class IPIP20
Shock resistance
acc. to IEC 60068-2-2715g / 11 ms
Vibration resistance1-6 Hz / 15 mm; 6-500 Hz / 2 g
Switching capacity current of the NO contacts of the relay outputs at AC-15
at 24 V6 A
at 120 V6 A
at 230 V3 A
Switching capacity current of the NO contacts of the relay outputs at DC-13
at 24 V2 A
at 60 V0.55 A
at 125 V0.25 A
Mechanical service life (switching cycles)
typical10 000 000
Electrical endurance (switching cycles)
typical100 000
Buffering time in the event of power failure0.05 s
Reference code acc. to DIN EN 81346-2F
Continuous current of the NO contacts of the relay outputs
at 50 °C6 A
at 60 °C5 A
Type of input characteristicType 1 in accordance with EN 61131-2
Electromagnetic compatibility
EMC emitted interference
acc. to IEC 60947-1class A
EMI immunity acc. to IEC 60947-1corresponds to degree of severity 3
Conducted interference
due to burst acc. to IEC 61000-4-42 kV (power ports) / 1 kV (signal ports)
due to conductor-earth surge acc. to IEC 61000-4-52 kV
due to conductor-conductor surge acc. to IEC 61000-4-51 kV
due to high-frequency radiation acc. to IEC 61000-4-610 V
Field-bound parasitic coupling acc. to IEC 61000-4-310 V/m
Electrostatic discharge acc. to IEC 61000-4-26 kV contact discharge / 8 kV air discharge
Conducted HF-interference emissions acc. to CISPR11corresponds to degree of severity A
Field-bound HF-interference emission acc. to CISPR11corresponds to degree of severity A
Inputs/ Outputs
Product function
Parameterizable inputsYes
Parameterizable outputsYes
Number of inputs4
for thermistor connection1
Number of digital inputs
with a common reference potential4
Digital input version
Type 1 acc. to IEC 61131Yes
Input voltage at digital input at DC rated value24 V
Number of outputs3
Number of semiconductor outputs0
Number of outputs as contact-affected switching element3
Switching behaviormonostable
Type of relay outputsMonostable
Wire length for digital signals maximum300 m
Wire length for thermistor connection
with conductor cross-section = 0.5 mm² maximum50 m
with conductor cross-section = 1.5 mm² maximum150 m
with conductor cross-section = 2.5 mm² maximum250 m
Protective and monitoring functions
Product function
Phase unbalanceYes
blocking current evaluationYes
power factor monitoringNo
Ground fault detectionYes
Phase failure detectionYes
phase sequence recognitionNo
voltage detectionNo
Monitoring of number of start operationsYes
Overvoltage detectionNo
Overcurrent detection 1 phaseYes
undervoltage detectionNo
undercurrent detection 1 phaseYes
active power monitoringNo
Product function
Current detectionYes
Overload protectionYes
Evaluation of thermistor motor protectionYes
Total cold resistance number of sensors in series maximum1.5 kΩ
Response value of thermoresistor3 400 ... 3 800 Ω
of the short-circuit control9 Ω
Release value of thermoresistor1 500 ... 1 650 Ω
Explosion device group and category acc. to ATEX product directive 94/9/ECEx II (2) GD / Ex I (M2)
Motor control functions
Product function
parameterizable overload relayYes
circuit breaker controlYes
direct startYes
reverse startingYes
star-delta circuitNo
star-delta reversing circuitNo
Dahlander circuitNo
Dahlander reversing circuitNo
pole-changing switch circuitNo
pole-changing switch reversing circuitNo
Slide controlNo
valve controlNo
Communication/ Protocol
Protocol is supported PROFIBUS DP protocolYes
Protocol is supported PROFINET IO protocolNo
Protocol is supported PROFIsafe protocolNo
Protocol is supported Modbus RTUNo
Protocol is supported EtherNet/IPNo
Protocol is supported OPC UA ServerNo
Protocol is supported LLDPNo
Protocol is supported Address Resolution Protocol (ARP)No
Protocol is supported SNMPNo
Protocol is supported HTTPSNo
Protocol is supported NTPNo
Protocol is supported Media Redundancy Protocol (MRP)No
Product function is supported Device Level Ring (DLR)No
Number of interfaces
acc. to PROFINET0
acc. to PROFIBUS1
according to Ethernet/IP0
Product function
web serverNo
shared deviceNo
at the Ethernet interface AutocrossoverNo
at the Ethernet interface AutonegotiationNo
at the Ethernet interface AutosensingNo
is supported PROFINET system redundancyNo
supports PROFIenergy measured valuesNo
supports PROFIenergy shutdownNo
Transfer rate maximum12 Mbit/s
Identification & maintenance function
I&M0 - device-specific informationYes
I&M1 – higher-level designation/location designationYes
I&M2 - installation dateYes
I&M3 - commentYes
Type of electrical connection
of the communication interface9-pin SUB-D socket (12 Mbit) / screw terminal (1.5 Mbit)
Installation/ mounting/ dimensions
Mounting positionany
Mounting typescrew and snap-on mounting
Height111 mm
Width45 mm
Depth95 mm
Required spacing
top40 mm
bottom40 mm
left0 mm
right0 mm
Connections/Terminals
Product function
removable terminal for auxiliary and control circuitYes
Type of electrical connection
for auxiliary and control current circuitscrew-type terminals
Type of connectable conductor cross-sections
solid1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²)
finely stranded with core end processing1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²)
at AWG conductors solid1x (20 ... 12), 2x (20 ... 14)
at AWG conductors stranded1x (20 ... 14), 2x (20 ... 16)
Tightening torque
with screw-type terminals0.8 ... 1.2 N·m
Tightening torque [lbf·in]
with screw-type terminals7 ... 10.3 lbf·in
Type of connectable conductor cross-sections for PROFIBUS wire2x 0.34 mm², AWG 22
Ambient conditions
Installation altitude at height above sea level
1 maximum2 000 m
2 maximum3 000 m; max. +50 °C (no protective separation)
3 maximum4 000 m; No protective separation at 40 °C
Ambient temperature
during operation-25 ... +60 °C
during storage-40 ... +80 °C
during transport-40 ... +80 °C
Environmental category
during operation acc. to IEC 607213K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6
during storage acc. to IEC 607211K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4
during transport acc. to IEC 607212K2, 2C1, 2S1, 2M2
Relative humidity
during operation5 ... 95 %
Contact rating of auxiliary contacts according to ULB300 / R300
Short-circuit protection
Design of short-circuit protection
per outputFuse links: gG 6 A, quick-response 10 A (IEC 60947-5-1), miniature circuit-breaker C char.: 1.6 A (IEC 60947-5-1) or 6 A (I_K < 500 A)
Safety related data
Protection against electrical shockfinger-safe
Control circuit/ Control
Product function soft starter controlNo
Type of voltage of the control supply voltageDC
Control supply voltage 1
at DC rated value24 V
Operating range factor control supply voltage rated value at DC
initial value0.8
Full-scale value1.2

External links