| Basic unit SIMOCODE pro C, PROFIBUS DP interface 12 Mbit/s, RS 485, 4I/3O freely parameterizable, Us: 24 V DC, input for thermistor connection Monostable relay outputs |
Product brand name | SIRIUS |
Product designation | Motor management system |
Design of the product | basic unit 1 |
Product type designation | SIMOCODE pro C |
General technical data |
Product function | |
Bus communication | Yes |
data acquisition function | Yes |
Diagnostics function | Yes |
Password protection | Yes |
Test function | Yes |
maintenance function | Yes |
Product component | |
input for thermistor connection | Yes |
Digital input | Yes |
input for analog temperature sensors | No |
input for ground fault detection | No |
Relay output | Yes |
Product extension | |
Temperature monitoring module | No |
Current measuring module | Yes |
Current/voltage measuring module | No |
failsafe digital I/O module | No |
Ground fault monitoring module | No |
Control unit with display | No |
Control unit | Yes |
analog I/O module | No |
Consumed active power | 5 W |
Insulation voltage | |
with degree of pollution 3 rated value | 300 V |
Surge voltage resistance rated value | 4 000 V |
Protection class IP | IP20 |
Shock resistance | |
acc. to IEC 60068-2-27 | 15g / 11 ms |
Vibration resistance | 1-6 Hz / 15 mm; 6-500 Hz / 2 g |
Switching capacity current of the NO contacts of the relay outputs at AC-15 | |
at 24 V | 6 A |
at 120 V | 6 A |
at 230 V | 3 A |
Switching capacity current of the NO contacts of the relay outputs at DC-13 | |
at 24 V | 2 A |
at 60 V | 0.55 A |
at 125 V | 0.25 A |
Mechanical service life (switching cycles) | |
typical | 10 000 000 |
Electrical endurance (switching cycles) | |
typical | 100 000 |
Buffering time in the event of power failure | 0.05 s |
Reference code acc. to DIN EN 81346-2 | F |
Continuous current of the NO contacts of the relay outputs | |
at 50 °C | 6 A |
at 60 °C | 5 A |
Type of input characteristic | Type 1 in accordance with EN 61131-2 |
Electromagnetic compatibility |
EMC emitted interference | |
acc. to IEC 60947-1 | class A |
EMI immunity acc. to IEC 60947-1 | corresponds to degree of severity 3 |
Conducted interference | |
due to burst acc. to IEC 61000-4-4 | 2 kV (power ports) / 1 kV (signal ports) |
due to conductor-earth surge acc. to IEC 61000-4-5 | 2 kV |
due to conductor-conductor surge acc. to IEC 61000-4-5 | 1 kV |
due to high-frequency radiation acc. to IEC 61000-4-6 | 10 V |
Field-bound parasitic coupling acc. to IEC 61000-4-3 | 10 V/m |
Electrostatic discharge acc. to IEC 61000-4-2 | 6 kV contact discharge / 8 kV air discharge |
Conducted HF-interference emissions acc. to CISPR11 | corresponds to degree of severity A |
Field-bound HF-interference emission acc. to CISPR11 | corresponds to degree of severity A |
Inputs/ Outputs |
Product function | |
Parameterizable inputs | Yes |
Parameterizable outputs | Yes |
Number of inputs | 4 |
for thermistor connection | 1 |
Number of digital inputs | |
with a common reference potential | 4 |
Digital input version | |
Type 1 acc. to IEC 61131 | Yes |
Input voltage at digital input at DC rated value | 24 V |
Number of outputs | 3 |
Number of semiconductor outputs | 0 |
Number of outputs as contact-affected switching element | 3 |
Switching behavior | monostable |
Type of relay outputs | Monostable |
Wire length for digital signals maximum | 300 m |
Wire length for thermistor connection | |
with conductor cross-section = 0.5 mm² maximum | 50 m |
with conductor cross-section = 1.5 mm² maximum | 150 m |
with conductor cross-section = 2.5 mm² maximum | 250 m |
Protective and monitoring functions |
Product function | |
Phase unbalance | Yes |
blocking current evaluation | Yes |
power factor monitoring | No |
Ground fault detection | Yes |
Phase failure detection | Yes |
phase sequence recognition | No |
voltage detection | No |
Monitoring of number of start operations | Yes |
Overvoltage detection | No |
Overcurrent detection 1 phase | Yes |
undervoltage detection | No |
undercurrent detection 1 phase | Yes |
active power monitoring | No |
Product function | |
Current detection | Yes |
Overload protection | Yes |
Evaluation of thermistor motor protection | Yes |
Total cold resistance number of sensors in series maximum | 1.5 kΩ |
Response value of thermoresistor | 3 400 ... 3 800 Ω |
of the short-circuit control | 9 Ω |
Release value of thermoresistor | 1 500 ... 1 650 Ω |
Explosion device group and category acc. to ATEX product directive 94/9/EC | Ex II (2) GD / Ex I (M2) |
Motor control functions |
Product function | |
parameterizable overload relay | Yes |
circuit breaker control | Yes |
direct start | Yes |
reverse starting | Yes |
star-delta circuit | No |
star-delta reversing circuit | No |
Dahlander circuit | No |
Dahlander reversing circuit | No |
pole-changing switch circuit | No |
pole-changing switch reversing circuit | No |
Slide control | No |
valve control | No |
Communication/ Protocol |
| |
Protocol is supported PROFIBUS DP protocol | Yes |
Protocol is supported PROFINET IO protocol | No |
Protocol is supported PROFIsafe protocol | No |
Protocol is supported Modbus RTU | No |
Protocol is supported EtherNet/IP | No |
Protocol is supported OPC UA Server | No |
Protocol is supported LLDP | No |
Protocol is supported Address Resolution Protocol (ARP) | No |
Protocol is supported SNMP | No |
Protocol is supported HTTPS | No |
Protocol is supported NTP | No |
Protocol is supported Media Redundancy Protocol (MRP) | No |
Product function is supported Device Level Ring (DLR) | No |
Number of interfaces | |
acc. to PROFINET | 0 |
acc. to PROFIBUS | 1 |
according to Ethernet/IP | 0 |
Product function | |
web server | No |
shared device | No |
at the Ethernet interface Autocrossover | No |
at the Ethernet interface Autonegotiation | No |
at the Ethernet interface Autosensing | No |
is supported PROFINET system redundancy | No |
supports PROFIenergy measured values | No |
supports PROFIenergy shutdown | No |
Transfer rate maximum | 12 Mbit/s |
Identification & maintenance function | |
I&M0 - device-specific information | Yes |
I&M1 – higher-level designation/location designation | Yes |
I&M2 - installation date | Yes |
I&M3 - comment | Yes |
Type of electrical connection | |
of the communication interface | 9-pin SUB-D socket (12 Mbit) / screw terminal (1.5 Mbit) |
Installation/ mounting/ dimensions |
Mounting position | any |
Mounting type | screw and snap-on mounting |
Height | 111 mm |
Width | 45 mm |
Depth | 95 mm |
Required spacing | |
top | 40 mm |
bottom | 40 mm |
left | 0 mm |
right | 0 mm |
Connections/Terminals |
Product function | |
removable terminal for auxiliary and control circuit | Yes |
Type of electrical connection | |
for auxiliary and control current circuit | screw-type terminals |
Type of connectable conductor cross-sections | |
solid | 1x (0.5 ... 4.0 mm²), 2x (0.5 ... 2.5 mm²) |
finely stranded with core end processing | 1x (0.5 ... 2.5 mm²), 2x (0.5 ... 1.5 mm²) |
at AWG conductors solid | 1x (20 ... 12), 2x (20 ... 14) |
at AWG conductors stranded | 1x (20 ... 14), 2x (20 ... 16) |
Tightening torque | |
with screw-type terminals | 0.8 ... 1.2 N·m |
Tightening torque [lbf·in] | |
with screw-type terminals | 7 ... 10.3 lbf·in |
Type of connectable conductor cross-sections for PROFIBUS wire | 2x 0.34 mm², AWG 22 |
Ambient conditions |
Installation altitude at height above sea level | |
1 maximum | 2 000 m |
2 maximum | 3 000 m; max. +50 °C (no protective separation) |
3 maximum | 4 000 m; No protective separation at 40 °C |
Ambient temperature | |
during operation | -25 ... +60 °C |
during storage | -40 ... +80 °C |
during transport | -40 ... +80 °C |
Environmental category | |
during operation acc. to IEC 60721 | 3K6 (no formation of ice, no condensation, relative humidity 10 ... 95%), 3C3 (no salt mist), 3S2 (sand must not get into the devices), 3M6 |
during storage acc. to IEC 60721 | 1K6 (no condensation, relative humidity 10 ... 95%), 1C2 (no salt mist), 1S2 (sand must not get into the devices), 1M4 |
during transport acc. to IEC 60721 | 2K2, 2C1, 2S1, 2M2 |
Relative humidity | |
during operation | 5 ... 95 % |
Contact rating of auxiliary contacts according to UL | B300 / R300 |
Short-circuit protection |
Design of short-circuit protection | |
per output | Fuse links: gG 6 A, quick-response 10 A (IEC 60947-5-1), miniature circuit-breaker C char.: 1.6 A (IEC 60947-5-1) or 6 A (I_K < 500 A) |
Safety related data |
Protection against electrical shock | finger-safe |
Control circuit/ Control |
Product function soft starter control | No |
Type of voltage of the control supply voltage | DC |
Control supply voltage 1 | |
at DC rated value | 24 V |
Operating range factor control supply voltage rated value at DC | |
initial value | 0.8 |
Full-scale value | 1.2 |