3RU2136-4HB1
THERM. OVERLOAD RELAY 40 - 50 A

From SIEMENS

Overload relay 40... 50 A for motor protection Size S2, CLASS 10 Stand-alone installation Main circuit: Screw Auxiliary circuit: Screw Manual-Automatic-Reset
Product brand nameSIRIUS
Product designationthermal overload relay
Product type designation3RU2
General technical data
Size of overload relayS2
Size of contactor can be combined company-specificS2
Power loss [W] total typical11 W
Insulation voltage with degree of pollution 3 rated value690 V
Surge voltage resistance rated value6 kV
maximum permissible voltage for safe isolation
in networks with grounded star point between auxiliary and auxiliary circuit415 V
in networks with grounded star point between auxiliary and auxiliary circuit415 V
in networks with grounded star point between main and auxiliary circuit690 V
in networks with grounded star point between main and auxiliary circuit690 V
Protection class IP
on the frontIP20
of the terminalIP00
Shock resistance
acc. to IEC 60068-2-278g / 11 ms
Recovery time
after overload trip with automatic reset typical10 min
after overload trip with remote-reset10 min
after overload trip with manual reset10 min
Type of protectionEx e
Certificate of suitability relating to ATEXDMT 98 ATEX G 001
Protection against electrical shockfinger-safe when touched vertically from front acc. to IEC 60529
Reference code acc. to DIN EN 81346-2F
Ambient conditions
Installation altitude at height above sea level
maximum2 000 m
Temperature compensation-40 ... +60 °C
Relative humidity during operation0 ... 90 %
Main circuit
Number of poles for main current circuit3
Adjustable pick-up value current of the current-dependent overload release40 ... 50 A
Operating voltage
rated value690 V
at AC-3 rated value maximum690 V
Operating frequency rated value50 ... 60 Hz
Operating current rated value50 A
Auxiliary circuit
Design of the auxiliary switchintegrated
Number of NC contacts for auxiliary contacts1
Notefor contactor disconnection
Number of NO contacts for auxiliary contacts1
Notefor message "Tripped"
Number of CO contacts
for auxiliary contacts0
Operating current of auxiliary contacts at AC-15
at 24 V3 A
at 110 V3 A
at 120 V3 A
at 125 V3 A
at 230 V2 A
at 400 V1 A
Operating current of auxiliary contacts at DC-13
at 24 V2 A
at 110 V0.22 A
at 125 V0.22 A
at 220 V0.11 A
Design of the miniature circuit breaker
for short-circuit protection of the auxiliary switch required6A (SCC less than equal to 0.5 kA; U less than equal to 260V)
Contact rating of auxiliary contacts according to ULB600 / R300
Protective and monitoring functions
Trip classCLASS 10
Design of the overload releasethermal
UL/CSA ratings
Full-load current (FLA) for three-phase AC motor
at 480 V rated value50 A
at 600 V rated value50 A
Short-circuit protection
Design of the fuse link
for short-circuit protection of the auxiliary switch requiredfuse gG: 6 A, quick: 10 A
Installation/ mounting/ dimensions
Mounting positionany
Mounting typestand-alone installation
Height105 mm
Width55 mm
Depth117 mm
Required spacing
with side-by-side mounting
— forwards10 mm
— Backwards0 mm
— upwards10 mm
— downwards10 mm
— at the side10 mm
for grounded parts
— forwards10 mm
— Backwards0 mm
— upwards10 mm
— at the side10 mm
— downwards10 mm
for live parts
— forwards10 mm
— Backwards0 mm
— upwards10 mm
— downwards10 mm
— at the side10 mm
Connections/Terminals
Product function
removable terminal for auxiliary and control circuitNo
Type of electrical connection
for main current circuitscrew-type terminals
for auxiliary and control current circuitscrew-type terminals
Arrangement of electrical connectors for main current circuitTop and bottom
Type of connectable conductor cross-sections
for main contacts
— single or multi-stranded2x (1 ... 35 mm²), 1x (1 ... 50 mm²)
— finely stranded with core end processing2x (1 ... 25 mm²), 1x (1 ... 35 mm²)
at AWG conductors for main contacts2x (18 ... 2), 1x (18 ... 1)
Type of connectable conductor cross-sections
for auxiliary contacts
— single or multi-stranded2x (0,5 ... 1,5 mm²), 2x (0,75 ... 2,5 mm²)
— finely stranded with core end processing2x (0.5 ... 1.5 mm²), 2x (0.75 ... 2.5 mm²)
at AWG conductors for auxiliary contacts2x (20 ... 16), 2x (18 ... 14)
Tightening torque
for main contacts with screw-type terminals3 ... 4.5 N·m
for auxiliary contacts with screw-type terminals0.8 ... 1.2 N·m
Design of screwdriver shaft5 ... 6 mm diameter
Size of the screwdriver tipPozidriv PZ 2
Design of the thread of the connection screw
for main contactsM6
of the auxiliary and control contactsM3
Safety related data
T1 value for proof test interval or service life acc. to IEC 6150820 y
Display
Display version
for switching statusSlide switch